T-type compensating lead wire
Product Details
Product Overview
T-type compensating lead wire
This product is suitable for electrical connection between various thermocouples with graduation marks of S, R, K, E, T, J, and N types and temperature display instruments, aiming to enhance temperature measurement accuracy. Compensation wires are categorized into extension and compensation types.
Compensation conductors are classified into precision grade (symbol S) and general grade (no symbol) based on different tolerances of their thermoelectric characteristics.
Operating characteristics of compensating lead wire products: The compensating lead wire can operate in an environment ranging from -60 to 260℃, making it an ideal automation component. It has been widely used for single-point or multi-point connections in automatic temperature measurement instruments in sectors such as petroleum, chemical, metallurgical, and electric power.
Product standard: Compensating conductor: GB/T4989-94: Q/ 3 20831SQL07-96
Service characteristics: Operating temperature: Heat resistance levels: -65~200℃ and -65~260℃;
General grade: two types, -40~70℃ and -40~105℃;
Bending radius: Compensating conductor: not less than 8 times the outer diameter of the conductor;
Product standard: Thermocouple compensating lead wire: GB/T4989-94
Thermocouple compensating cable: Q/3 20831SQL07-96 Operating characteristics: Operating temperature: Heat resistance grade: -65~200℃ and -65~260℃;
Ordinary grade: two types, -40~70℃ and -40~105℃;
Bending radius: Compensating conductor: not less than 8 times the outer diameter of the conductor;
Compensating cable: not less than 12 times the cable's outer diameter when armored, and not less than 6 times the cable's outer diameter when unarmored
Product Model
Model Name
KX-FF fluoroplastic insulated and fluoroplastic sheathed compensating cable for ordinary grade K-scale thermocouple
KX-FPF fluoroplastic insulated fluoroplastic sheathed copper wire braided individual shielding ordinary grade K scale thermocouple compensating cable
KX-FPFP fluoroplastic insulated fluoroplastic sheathed copper wire braided individual and overall shielding ordinary grade K scale thermocouple compensating cable
KX-FFP fluoroplastic insulated fluoroplastic sheathed copper wire braided overall shielding general grade K scale thermocouple compensating cable
KXS-FF fluoroplastic insulated and fluoroplastic sheathed compensating cable for precision grade K-scale thermocouple
KXS-FPF fluoroplastic insulated fluoroplastic sheathed copper wire braided individual shield precision grade K scale thermocouple compensating cable
KXS-FPFP fluoroplastic insulated fluoroplastic sheathed copper wire braided individual and overall shielding precision grade K scale thermocouple compensating cable
KXS-FFP fluoroplastic insulated fluoroplastic sheathed copper wire braided overall shielding precision grade K scale thermocouple compensating cable
KX-FP3F fluoroplastic insulated aluminum/plastic composite tape individually shielded fluoroplastic sheathed compensating cable for ordinary grade K scale thermocouple
KX-FP3FP3 fluoroplastic insulated aluminum/plastic composite tape sub-shield and overall shield fluoroplastic sheathed ordinary grade K scale thermocouple compensating cable
KX-FFP3 fluoroplastic insulated fluoroplastic sheathed copper wire braided aluminum/plastic composite tape overall shielding general grade K scale thermocouple compensating cable
KXS-FP3F fluoroplastic insulated aluminum/plastic composite tape individually shielded fluoroplastic sheathed precision grade K scale thermocouple compensating cable
KXS-FFP3 fluoroplastic insulated and sheathed aluminum/plastic composite tape overall shielding precision grade K scale thermocouple compensating cable
KXS-FP3FP3 fluoroplastic insulated aluminum/plastic composite tape sub-shield and overall shield fluoroplastic sheathed precision grade K scale thermocouple compensating cable
Product Features:
Note:
For other types of compensating cables such as EX, SC, KC, NC, NX, BC, TX, and JX, only the model number needs to be changed, such as EX-FF, EX-FPF, etc.
2. For copper tape shielded cables, simply replace P3 in the model number with P2. For example, KX-FP2F is a fluoroplastic insulated copper tape wrapped sub-shielded fluoroplastic sheathed compensating cable for ordinary grade K-scale thermocouples.
3. There are also some specially made high-temperature compensating cables with PTFE and glass fiber composite insulation and sheath, such as KXHF4