Home > Products > Compensation wire >
KC compensating wire
Product Details
The compensating lead wires or cables used in intrinsically safe explosion-proof temperature measurement systems are constructed with low capacitance and low inductance materials, ensuring explosion-proof safety performance. They are suitable for connecting explosion-proof thermocouple cold junctions and explosion-proof temperature measurement instruments in hazardous environments, forming an intrinsically safe thermocouple temperature measurement system.
II: Product implementation standards
GB/T4989-94 (equivalent to IEC584-3 standard)
III: Usage characteristics
1. Maximum operating temperature of conductor: heat-resistant grade: polyperfluoroethylene propylene (F46) 200℃
Soluble polytetrafluoroethylene at 260℃
Silicone rubber at 180℃
Ordinary grade: PVC at 70℃ and 105℃, XLPE at 90℃
Low-smoke, halogen-free, flame-retardant polyolefin at 70℃, and cross-linked types at 90℃ and 125℃
2. Low ambient temperature: PVC sheath: fixed installation -40℃, non-fixed installation -15℃
Fluoroplastic insulation and sheath: Fixed installation -60℃, non-fixed installation -20℃
3. Allowable bending radius of cable: For non-armored cables, the minimum is 6 times the outer diameter
The minimum length of copper tape shielding or steel tape armor for cables is 12 times the cable's outer diameter
The minimum thickness of fluoroplastic insulation and sheath is 10 times the outer diameter of the cable
Prev:Nothing